Table 451:
PSPTUV Group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Voltage block value
0.01...1.00
xUn
0.01
0.20
Internal blocking level
Enable block value
0=False
1=True
1=True
Enable Internal Blocking
Table 452:
PSPTUV Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Operation
1=on
5=off
1=on
Operation Off / On
Table 453:
PSPTUV Non group settings (Advanced)
Parameter
Values (Range)
Unit
Step
Default
Description
Reset delay time
0...60000
ms
1
20
Reset delay time
Relative hysteresis
1.0...5.0
%
0.1
4.0
Relative hysteresis for operation
4.4.5.8
Monitored data
Table 454:
PSPTUV Monitored data
Name
Type
Values (Range)
Unit
Description
START_DUR
FLOAT32
0.00...100.00
%
Ratio of start time /
operate time
PSPTUV
Enum
1=on
2=blocked
3=test
4=test/blocked
5=off
Status
4.4.5.9
Technical data
Table 455:
PSPTUV Technical data
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured
voltage: f
n
±2 Hz
±1.5% of the set value or ±0.002 × U
n
Start time
1)2)
Minimum
Typical
Maximum
U
Fault
= 0.99 × set
Start
value
U
Fault
= 0.9 × set
Start
value
52 ms
44 ms
55 ms
47 ms
58 ms
50 ms
Reset time
Typically 40 ms
Reset ratio
Depends on the set
Relative hysteresis
Table continues on next page
Section 4
1MRS758755 A
Protection functions
434
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...