![ABB RELION Series Technical Manual Download Page 612](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191612.webp)
GUID-36839B06-10FE-46FA-8289-5AA1EBBCD0FA V1 EN
Figure 307:
Condition for enabling the close request (CL_REQ) for CBXCBR
When the open command is given from communication, via LHMI or activating the
AU_OPEN
input, it is processed only if
OPEN_ENAD
is TRUE.
OP_REQ
output is also
available.
GUID-0683760A-9832-4A01-8E87-6E3A7E6FDFC3 V1 EN
Figure 308:
Condition for enabling the open request (OP_REQ) for CBXCBR
OPEN and CLOSE outputs
The
EXE_OP
output is activated when the open command is given (
AU_OPEN
, via
communication or from LHMI) and
OPEN_ENAD
signal is TRUE. In addition, the
protection trip commands can be routed through the CBXCBR function by using the
TRIP
input. When the
TRIP
input is TRUE, the
EXE_OP
output is activated
immediately and bypassing all enabling or blocking conditions.
The
EXE_CL
output is activated when the close command is given (
AU_CLOSE
, via
communication or from LHMI) and
CLOSE_ENAD
signal is TRUE. When the
TRIP
input is “TRUE”, CB closing is not allowed.
Section 9
1MRS758755 A
Control functions
606
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...