The operate times for the ANSI and IEC IDMT curves are defined with the
coefficients A, B and C.
The values of the coefficients can be calculated according to the formula:
t s
A
I
I
B
k
c
[ ]
=
>
−
+
⋅
1
A060821 V2 EN
(Equation 77)
t[s] Operate time in seconds
I
measured current
I>
set
Start value
k
set
Time multiplier
Table 707:
Curve parameters for ANSI and IEC IDMT curves
Curve name
A
B
C
(1) ANSI Extremely
Inverse
28.2
0.1217
2.0
(2) ANSI Very Inverse
19.61
0.491
2.0
(3) ANSI Normal
Inverse
0.0086
0.0185
0.02
(4) ANSI Moderately
Inverse
0.0515
0.1140
0.02
(6) Long Time
Extremely Inverse
64.07
0.250
2.0
(7) Long Time Very
Inverse
28.55
0.712
2.0
(8) Long Time Inverse
0.086
0.185
0.02
(9) IEC Normal Inverse
0.14
0.0
0.02
(10) IEC Very Inverse
13.5
0.0
1.0
(11) IEC Inverse
0.14
0.0
0.02
(12) IEC Extremely
Inverse
80.0
0.0
2.0
(13) IEC Short Time
Inverse
0.05
0.0
0.04
(14) IEC Long Time
Inverse
120
0.0
1.0
1MRS758755 A
Section 11
General function block features
REC615 and RER615
717
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...