In the DT mode, the function operates after a predefined operate time and resets when
the fault current disappears. The IDMT mode provides current-dependent timer
characteristics.
The function contains a blocking functionality. It is possible to block function outputs,
timers or the function itself, if desired.
4.1.1.4
Operation principle
The function can be enabled and disabled with the
Operation
setting. The
corresponding parameter values are "On" and "Off".
The operation of (F)PHxPTOC can be described by using a module diagram. All the
modules in the diagram are explained in the next sections.
A070552 V1 EN
Figure 114:
Functional module diagram
Level detector
The measured phase currents are compared phasewise to the set
Start value
. If the
measured value exceeds the set
Start value
, the level detector reports the exceeding of
the value to the phase selection logic. If the
ENA_MULT
input is active, the
Start value
setting is multiplied by the
Start value Mult
setting.
The protection relay does not accept the
Start value
or
Start value Mult
setting if the product of these settings exceeds the
Start value
setting
range.
The start value multiplication is normally done when the inrush detection function
(INRPHAR) is connected to the
ENA_MULT
input.
Section 4
1MRS758755 A
Protection functions
202
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...