4.1.2.9
Settings
Table 250:
FDPHLPDOC Group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Start value
0.05...5.00
xIn
0.01
0.05
Start value
Operate delay time
40...200000
ms
10
40
Operate delay time
Operating curve type
1=ANSI Ext. inv.
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
-1=Recloser 1
-2=Recloser 2
-3=Recloser 3
-4=Recloser 4
-5=Recloser 5
-6=Recloser 6
-7=Recloser 7
-8=Recloser 8
-9=Recloser 8+
-10=Recloser 8*
-11=Recloser 9
-12=Recloser 11
-13=Recloser 13
-14=Recloser 14
-15=Recloser 15
-16=Recloser 16
-17=Recloser 17
-18=Recloser 18
-19=Recloser A
-20=Recloser B
-21=Recloser C
-22=Recloser D
-23=Recloser E
-24=Recloser F
-25=Recloser G
-26=Recloser H
-27=Recloser J
-28=Recloser Kg
-29=Recloser Kp
-30=Recloser L
-31=Recloser M
-32=Recloser N
-33=Recloser P
-34=Recloser R
-35=Recloser T
-36=Recloser V
-37=Recloser W
-38=Recloser Y
-39=Recloser Z
15=IEC Def. Time
Selection of time delay curve type
Table continues on next page
1MRS758755 A
Section 4
Protection functions
REC615 and RER615
243
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...