![ABB RELION Series Technical Manual Download Page 150](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191150.webp)
3.16.5.4
Settings
Table 145:
TOFGAPC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Off delay time 1
0...3600000
ms
10
0
Off delay time
Off delay time 2
0...3600000
ms
10
0
Off delay time
Off delay time 3
0...3600000
ms
10
0
Off delay time
Off delay time 4
0...3600000
ms
10
0
Off delay time
Off delay time 5
0...3600000
ms
10
0
Off delay time
Off delay time 6
0...3600000
ms
10
0
Off delay time
Off delay time 7
0...3600000
ms
10
0
Off delay time
Off delay time 8
0...3600000
ms
10
0
Off delay time
3.16.5.5
Technical data
Table 146:
TOFGAPC Technical data
Characteristic
Value
Operate time accuracy
±1.0% of the set value or ±20 ms
3.16.6
Time delay on (8 pcs) TONGAPC
3.16.6.1
Function block
GUID-B694FC27-E6AB-40FF-B1C7-A7EB608D6866 V1 EN
Figure 91:
Function block
3.16.6.2
Functionality
The time delay on (8 pcs) function TONGAPC can be used, for example, for time-
delaying the output related to the input signal. TONGAPC contains eight independent
timers. The timer has a settable time delay. Once the input is activated, the output is
set after the time set by the
On delay time
setting has elapsed.
Section 3
1MRS758755 A
Basic functions
144
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...