3.15.3.2
Functionality
The QTY_GOOSE_COMM function block evaluates the peer device communication
status from the quality bits of the input signal and passes it as a Boolean signal to the
application.
The
IN
input can be connected to any GOOSE application logic output signal, for
example, GOOSERCV_BIN.
The
OUT
output indicates the communication status of the GOOSE function block.
When the output is in the true (1) state, the GOOSE communication is active. The
value false (0) indicates communication timeout.
3.15.3.3
Signals
Table 64:
QTY_GOOSE_COMM Input signals
Name
Type
Default
Description
IN
Any
0
Input signal
Table 65:
QTY_GOOSE_COMM Output signals
Name
Type
Description
COMMVALID
BOOLEAN
Output signal
3.15.4
T_HEALTH function block
3.15.4.1
Function block
GUID-B5FCAE66-8026-4D5F-AC38-028E5A8171BB V1 EN
Figure 59:
Function block
3.15.4.2
Functionality
The T_HEALTH function evaluates enumerated data of “Health” data attribute. This
function block can only be used with GOOSE.
The IN input can be connected to GOOSERCV_ENUM function block, which is
receiving the LD0.LLN0.Health.stVal data attribute sent by another device.
The outputs
OK
,
WARNING
and
ALARM
are extracted from the enumerated input
value. Only one of the outputs can be active at a time. In case the
Section 3
1MRS758755 A
Basic functions
114
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...