![ABB RELION Series Technical Manual Download Page 688](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191688.webp)
this voltage level to avoid the undesired voltage dip or swell indications. This is
accomplished by converting the variation limits with the
Reference voltage
setting in
the variation detection module, that is, when there is a voltage different from the
nominal voltage, the
Reference voltage
setting is set to this voltage.
The
Variation enable
setting is used for enabling or disabling the variation types. By
default, the setting value is "Swell+dip+Int" and all the alternative variation types are
indicated. For example, for setting "Swell+dip", the interruption detection is not
active and only swell or dip events are indicated.
In a case where
Phase mode
is "Single Phase" and the dip functionality is available,
the output
DIPST
is activated when the measured TRMS value drops below the
Voltage dip set 3
setting in one phase and also remains above the
Voltage Int set
setting. If the voltage drops below the
Voltage Int set
setting, the output
INTST
is
activated.
INTST
is deactivated when the voltage value rises above the setting
Voltage Int set
. When the same measured TRMS magnitude rises above the setting
Voltage swell set 3
, the
SWELLST
output is activated.
There are three setting value limits for dip (
Voltage dip set 1..3
) and swell activation
(
Voltage swell set 1..3
) and one setting value limit for interruption.
If
Phase mode
is "Three Phase", the
DIPST
and
INTST
outputs are
activated when the voltage levels of all monitored phases, defined
with the parameter
Phase supervision
, drop below the
Voltage Int set
setting value. An example for the detection principle of voltage
interruption for "Three Phase" when
Phase supervision
is "Ph A + B
+ C", and also the corresponding start signals when
Phase mode
is
"Single Phase", are as shown in the example for the detection of a
three-phase interruption.
Section 10
1MRS758755 A
Power quality measurement functions
682
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...