![ABB RELION Series Technical Manual Download Page 409](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191409.webp)
protection relay's program. The influence of the
BLOCK
signal activation is
preselected with the global setting
Blocking mode
.
The
Blocking mode
setting has three blocking methods. In the "Freeze timers" mode,
the operation timer is frozen to the prevailing value, but the
OPERATE
output is not
deactivated when blocking is activated. In the "Block all" mode, the whole function is
blocked and the timers are reset. In the "Block OPERATE output" mode, the function
operates normally but the
OPERATE
output is not activated.
4.3.2.5
Application
In three-phase distribution and subtransmission network applications the phase
discontinuity in one phase can cause an increase of zero-sequence voltage and short
overvoltage peaks and also oscillation in the corresponding phase.
PDNSPTOC is a three-phase protection with DT characteristic, designed for detecting
broken conductors in distribution and subtransmission networks. The function is
applicable for both overhead lines and underground cables.
The operation of PDNSPTOC is based on the ratio of the positive-sequence and
negative-sequence currents. This gives a better sensitivity and stability compared to
plain negative-sequence current protection since the calculated ratio of positive-
sequence and negative-sequence currents is relatively constant during load variations.
The unbalance of the network is detected by monitoring the negative-sequence and
positive-sequence current ratio, where the negative-sequence current value is I
2
and I
1
is the positive-sequence current value. The unbalance is calculated with the equation.
Iratio
I
I
=
2
1
A070702 V2 EN
(Equation 43)
Broken conductor fault situation can occur in phase A in a feeder.
1MRS758755 A
Section 4
Protection functions
REC615 and RER615
403
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...