A071107 V1 EN
Figure 283:
Travel time calculation when Travel time Clc mode is “From Pos to
Pos”
There is a time difference t
1
between the start of the main contact opening and the
opening of the
POSCLOSE
auxiliary contact. Similarly, there is a time gap t
2
between
the time when the
POSOPEN
auxiliary contact opens and the main contact is
completely open. To incorporate the time t
1
+ t
2
, a correction factor needs to be added
with t
open
to get the actual opening time. This factor is added with the
Opening time
Cor
(= t
1
+ t
2
) setting. The closing time is calculated by adding the value set with the
Closing time Cor
(t
3
+ t
4
) setting to the measured closing time.
When the setting
Travel time Clc mode
is “From Cmd to Pos”, the contact travel time
of the breaker is calculated from the time between the circuit breaker opening or
closing command and the auxiliary contacts’ state change. The opening travel time is
measured between the rising edge of the OPEN_CB_EXE command and the
POSOPEN
auxiliary contact. The closing travel time is measured between the rising
edge of the CLOSE_CB_EXEC command and the POSCLOSE auxiliary contact.
1MRS758755 A
Section 7
Condition monitoring functions
REC615 and RER615
539
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...