Common signals
The VALID output indicates the validity of received GOOSE data, which means in
case of valid, that the GOOSE communication is working and received data quality
bits (if configured) indicate good process data. Invalid status is caused either by bad
data quality bits or GOOSE communication failure. See IEC 61850 engineering guide
for details.
The OUT output passes the received GOOSE value for the application. Default value
(0) is used if VALID output indicates invalid status. The IN input is defined in the
GOOSE configuration and can always be seen in SMT sheet.
Settings
3.14.1
GOOSERCV_BIN function block
3.14.1.1
Function block
GUID-44EF4D6E-7389-455C-BDE5-B127678E2CBC V1 EN
Figure 48:
Function block
3.14.1.2
Functionality
The GOOSERCV_BIN function is used to connect the GOOSE binary inputs to the
application.
3.14.1.3
Signals
Table 52:
GOOSERCV_BIN Output signals
Name
Type
Description
OUT
BOOLEAN
Output signal
VALID
BOOLEAN
Output signal
3.14.2
GOOSERCV_DP function block
3.14.2.1
Function block
GUID-63C0C3EE-1C0E-4F78-A06E-3E84F457FC98 V1 EN
Figure 49:
Function block
1MRS758755 A
Section 3
Basic functions
REC615 and RER615
107
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...