13.4.7.1
COM0022 and COM0023 jumper locations and connections
The optional communication module COM0022 supports EIA-232/EIA-485 serial
communication (X6 connector). Only COM1 (X6 connector) is used for serial
communication.
Connector X5 on COM0022 is dedicated to IRIG-B.
Table 718:
Configuration options of the communication port for COM0022
COM1 connector X6
EIA-232
EIA-485 2-wire
EIA-485 4-wire
The optional communication module COM0023 supports EIA-232/EIA-485 serial
communication (X6 connector), EIA-485 serial communication (X5 connector) and
optical ST serial communication (X12 connector).
Two independent communication ports are supported by COM0023. The two 2-wire
ports use COM1 and COM2. Alternatively, if only one 4-wire port is configured, it
uses COM2. The fibre-optic ST connection uses the COM1 port.
Table 719:
Configuration options of the communication ports for COM0023
COM1 connector X6
COM2 connector X5 or X12
EIA-232
Optical ST (X12)
EIA-485 2-wire
EIA-485 2-wire (X5)
EIA-485 4-wire
EIA-485 4-wire (X5)
1MRS758755 A
Section 13
Protection relay's physical connections
REC615 and RER615
771
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...