When the station authority level “L,S,R” is used, the control access can be selected
using R/L button or CONTROL function block. IEC 61850 data object
CTRL.LLN0.LocSta and CONTROL function block input
CTRL_STA
are applicable
for this station authority level.
Station control access can be reserved by using R/L button or CONTROL function
block together with IEC 61850 data object CTRL.LLN0.LocSta.
Table 168:
Station authority level “L,S,R” using R/L button
L/R Control
L/R Control status
Control access
R/L button
CTRL.LLN0.LocSta
1)
CTRL.LLN0.MltLev
L/R state
CTRL.LLN0.LocKeyHMI
Local user
IEC 61850
client
2)
IEC 61850
client
3)
Local
FALSE
FALSE
1
x
Remote
FALSE
FALSE
2
x
Remote
TRUE
FALSE
3
x
Off
FALSE
FALSE
0
1) Station client reserves the control operating by writing controllable point LocSta.
2) Client IEC 61850 command originator category is remote.
3) Client IEC 61850 command originator category is station.
Table 169:
Station authority level “L,S,R” using CONTROL function block
L/R Control
L/R Control status
Control access
Control FB input CTRL.LLN0.LocSta
1)
CTRL.LLN0.MltLev
L/R state
CTRL.LLN0.LocKeyHMI
Local user
IEC 61850
client
2)
IEC 61850
client
3)
CTRL_OFF
FALSE
FALSE
0
CTRL_LOC
FALSE
FALSE
1
x
CTRL_STA
TRUE
FALSE
3
x
CTRL_REM
4)
TRUE
FALSE
3
x
CTRL_REM
FALSE
FALSE
2
x
CTRL_ALL
FALSE
FALSE
0
1) Station client reserves the control operating by writing controllable point LocSta.
2) Client IEC 61850 command originator category is remote.
3) Client IEC 61850 command originator category is station.
4) CTRL_STA unconnected in application configuration. Station client reserves the control operating by writing controllable point LocSta.
3.16.11.7
Station authority level “L,S,S+R,L+S,L+S+R”
Station authority level “L,S,S+R,L+S,L+S+R” adds station control access together
with several different multilevel access scenarios. Control access can also be
simultaneously permitted from local, station or remote location. Simultaneous local,
station or remote control operation is not allowed as one client and location at time can
access controllable objects and they remain reserved until the previously started
control operation is first completed by the client.
1MRS758755 A
Section 3
Basic functions
REC615 and RER615
157
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...