![ABB RELION Series Technical Manual Download Page 499](http://html1.mh-extra.com/html/abb/relion-series/relion-series_technical-manual_3663191499.webp)
either given in ohm/km and section length in km, or ohm/mile and section length in
miles. The resulting Flt distance matches the units entered for the line section lengths.
Positive-sequence impedance values
Fault location requires accurate setting values for line impedances. Positive-sequence
impedances are required both for location of short circuits and earth faults. As data
sheet impedance per unit values are generally valid only for a certain tower
configuration, the values should be adjusted according to the actual installation
configuration. This minimizes the fault location errors caused by inaccurate settings.
The positive-sequence reactance per unit and per phase can be calculated with a
following approximation equation which applies to symmetrically transposed three-
phase aluminium overhead lines without ground wires.
X
a
r
km
n
en
1
4
10
2
0 5
≈
⋅
⋅
+
−
ω
ln
.
[
/
]
Ω
GUID-B7F3697A-7C8E-4BF6-A63C-7BFD307DD128 V2 EN
(Equation 59)
ω
n
2 × π × f
n
, where f
n
= fundamental frequency [Hz]
a
en
a
a
a
12
23
31
3
⋅
⋅
(
)
GUID-DA850ABF-239A-4AB5-B63B-F0B54557CF2E V2 EN
the geometric average of phase distances [m]
a
xy
distance [m] between phases x and y
r
radius [m] for single conductor
GUID-40949A85-D97F-4639-9D61-3CAE997D28D3 V2 EN
Figure 255:
Typical distribution line tower configurations
Example values of positive-sequence impedances for typical medium voltage
overhead-lines are given in the following tables.
Table 515:
Positive-sequence impedance values for typical 11 kV conductors, “Flat” tower
configuration assumed
Name
R1 [Ω/km]
X1 [Ω/km]
ACSR 50 SQ.mm
0.532
0.373
ACSR 500 SQ.mm
0.0725
0.270
1MRS758755 A
Section 5
Protection related functions
REC615 and RER615
493
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...