3.18.3
Configuration
The load profile record can be configured with the PCM600 tool or any tool
supporting the IEC 61850 standard.
The load profile record can be enabled or disabled with the
Operation
setting under the
Configuration/Load Profile Record
menu.
Each protection relay can be mapped to each of the quantity channels of the load
profile record. The mapping is done with the
Quantity selection
setting of the
corresponding quantity channel.
The IP number of the protection relay and the content of the
Bay name
setting are both included in the COMTRADE configuration file for
identification purposes.
The memory consumption of load profile record is supervised, and indicated with two
signals
MEM_WARN
and
MEM_ALARM
, which could be used to notify the customer that
recording should be backlogged by reading the recorded data from the protection
relay. The levels for MEM_WARN and MEM_ALARM are set by two parameters
Mem.warn level
and
Mem. Alarm level
.
3.18.4
Signals
Table 194:
LDPRLRC Output signals
Name
Type
Description
MEM_WARN
BOOLEAN
Recording memory warning status
MEM_ALARM
BOOLEAN
Recording memory alarm status
Section 3
1MRS758755 A
Basic functions
182
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...