It is often required that the total fault clearance time is less than the given critical time.
This time often depends on the ability to maintain transient stability in case of a fault
close to a power plant.
GUID-1A2C47ED-0DCF-4225-9294-2AEC97C14D5E V1 EN
Figure 240:
Timeline of the breaker failure protection
Timer 3
This module is activated by the
CB_FAULT
signal. Once activated, the timer runs
until the set
CB fault delay
value has elapsed. The time characteristic is according to
DT. When the operation timer has reached the maximum time value
CB fault delay
,
the
CB_FAULT_AL
output is activated. After the set time, an alarm is given so that the
circuit breaker can be repaired. A typical value is 5 s.
Retrip logic
The retrip logic provides the
TRRET
output, which can be used to give a retrip signal
for the main circuit breaker. Timer 1 activates the retrip logic. The operation of the
retrip logic depends on the
CB fail retrip mode
setting.
•
The retrip logic is inactive if the
CB fail retrip mode
setting is set to "Off".
•
If
CB fail retrip mode
is set to the "Current check" mode, the activation of the
retrip output
TRRET
depends on the
CB failure mode
setting.
•
If
CB failure mode
is set to the "Current" mode,
TRRET
is activated when
the value of any phase current exceeds the
Current value
setting. The
TRRET
output remains active for the time set with the
Trip pulse time
setting or until all phase current values drop below the
Current value
setting, whichever is longer.
•
If
CB failure mode
is set to the "Breaker status" mode,
TRRET
is activated
if the circuit breaker is in the closed position. The
TRRET
output remains
1MRS758755 A
Section 5
Protection related functions
REC615 and RER615
469
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...