GUID-27C77008-B292-4112-9CF6-4B95EE19B9EC V1 EN
Figure 162:
Example of INTRPTEF operation in ”Intermittent EF” mode in the
faulty feeder, Peak counter limit=3
The timer calculates the start duration value START_DUR which indicates the
percentage ratio of the start situation and the set operating time. The value is available
in the monitored data view.
Timer 2
If the function is used in the directional mode and an opposite direction transient is
detected, the
BLK_EF
output is activated for the fixed delay time of 25 ms. If the
START
output is activated when the
BLK_EF
output is active, the
BLK_EF
output is
deactivated.
Blocking logic
There are three operation modes in the blocking function. The operation modes are
controlled by the
BLOCK
input and the global setting
Configuration/System/
Blocking mode
which selects the blocking mode. The
BLOCK
input can be controlled
by a binary input, a horizontal communication input or an internal signal of the
protection relay's program. The influence of the
BLOCK
signal activation is
preselected with the global setting
Blocking mode
.
The
Blocking mode
setting has three blocking methods. In the "Freeze timers" mode,
the operation timer is frozen to the prevailing value. In the "Block all" mode, the whole
Section 4
1MRS758755 A
Protection functions
320
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...