If a moderate system operates at 50 Hz, an underfrequency should be set for different
steps from 49.2 Hz to 47.5 Hz in steps of 0.3 – 0.4 Hz. The operating time for the
underfrequency can be set from a few seconds to a few fractions of a second stepwise
from a higher frequency value to a lower frequency value.
Table 467:
Setting for a five-step underfrequency operation
Load-shedding steps
Start value Freq setting
Operate Tm Freq setting
1
0.984 · Fn (49.2 Hz)
45000 ms
2
0.978 · Fn (49.2 Hz)
30000 ms
3
0.968 · Fn (49.2 Hz)
15000 ms
4
0.958 · Fn (49.2 Hz)
5000ms
5
0.950 · Fn (49.2 Hz)
500 ms
The rate of change of frequency function is not instantaneous since the function needs
time to supply a stable value. It is recommended to have a time delay long enough to
take care of the signal noise.
Small industrial systems can experience the rate of change of frequency as large as 5
Hz/s due to a single event. Even large power systems can form small islands with a
large imbalance between the load and generation when severe faults or combinations
of faults are cleared. Up to 3 Hz/s has been experienced when a small island becomes
isolated from a large system. For normal severe disturbances in large power systems,
the rate of change of the frequency is much less, often just a fraction of 1.0 Hz/s.
Similarly, the setting for df/dt can be from 0.1 Hz/s to 1.2 Hz/s in steps of 0.1 Hz/s to
0.3 Hz/s for large distributed power networks, with the operating time varying from a
few seconds to a few fractions of a second. Here, the operating time should be kept in
minimum for the higher df/dt setting.
Table 468:
Setting for a five-step df/dt< operation
Load-shedding steps
Start value df/dt setting
Operate Tm df/dt setting
1
-0.005 · Fn /s (-0.25 Hz/s)
8000 ms
2
-0.010 · Fn /s (-0.25 Hz/s)
2000 ms
3
-0.015 · Fn /s (-0.25 Hz/s)
1000 ms
4
-0.020 · Fn /s (-0.25 Hz/s)
500 ms
5
-0.025 · Fn /s (-0.25 Hz/s)
250 ms
Once the frequency has stabilized, the shed load can be restored. The restoring
operation should be done stepwise, taking care that it does not lead the system back to
the emergency condition.
Section 4
1MRS758755 A
Protection functions
450
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...