GUID-B0611FF1-46FD-4E81-A11D-4721F0AF7BF8 V1 EN
(Equation 12)
Yo
Calculated neutral admittance [Siemens]
Io
fault
Residual current during the fault [Amperes]
Uo
fault
Residual voltage during the fault [Volts]
Io
prefault
Prefault residual current [Amperes]
Uo
prefault
Prefault residual voltage [Volts]
ΔIo
Change in the residual current due to fault [Amperes]
ΔUo
Change in the residual voltage due to fault [Volts]
Traditionally, admittance calculation is done with the calculation mode "Normal",
that is, with the current and voltage values directly measured during the fault. As an
alternative, by selecting the calculation mode "Delta", the prefault zero-sequence
asymmetry of the network can be removed from the admittance calculation.
Theoretically, this makes the admittance calculation totally immune to fault
resistance, that is, the estimated admittance value is not affected by fault resistance.
Utilization of the change in Uo and Io due to a fault in the admittance calculation also
mitigates the effects of the VT and CT measurement errors, thus improving the
measuring accuracy, the sensitivity and the selectivity of the protection.
Calculation mode "Delta" is recommended in case a high sensitivity
of the protection is required, if the network has a high degree of
asymmetry during the healthy state or if the residual current
measurement is based on sum connection, that is, the Holmgren
connection.
Neutral admittance calculation produces certain values during forward and reverse
faults.
Fault in reverse direction, that is, outside the protected feeder.
Yo
Y
Fdtot
= −
GUID-B6E3F720-1F9F-4C11-A5DC-722838E8CCDA V1 EN
(Equation 13)
≈ − ⋅
j
I
U
eFd
ph
GUID-19AA418B-9A0A-4CEE-8772-0CD3F595E63F V1 EN
(Equation 14)
Y
Fdtot
Sum of the phase-to-earth admittances (Y
FdA
, Y
FdB
, Y
FdC
) of the protected feeder
I
eFd
Magnitude of the earth-fault current of the protected feeder when the fault resistance is
zero ohm
U
ph
Magnitude of the nominal phase-to-earth voltage of the system
Section 4
1MRS758755 A
Protection functions
328
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...