Analog output range is from -2000000.0 to 2000000.0.
If the value of the
AIn_VALUE
input exceeds the analog input range,
AOn_VALUE
is set to 0.0.
If the result of
AIn_VALUE
multiplied by the
Scale ratio n
setting
exceeds the analog output range,
AOn_VALUE
shows the minimum or
maximum value, according to analog value range.
3.16.10.3
Signals
Table 160:
SCA4GAPC Input signals
Name
Type
Default
Description
AI1_VALUE
FLOAT32
0.0
Analog input value of channel 1
AI2_VALUE
FLOAT32
0.0
Analog input value of channel 2
AI3_VALUE
FLOAT32
0.0
Analog input value of channel 3
AI4_VALUE
FLOAT32
0.0
Analog input value of channel 4
Table 161:
SCA4GAPC Output signals
Name
Type
Description
AO1_VALUE
FLOAT32
Analog value 1 after scaling
AO2_VALUE
FLOAT32
Analog value 2 after scaling
AO3_VALUE
FLOAT32
Analog value 3 after scaling
AO4_VALUE
FLOAT32
Analog value 4 after scaling
3.16.10.4
Settings
Table 162:
SCA4GAPC Non group settings (Basic)
Parameter
Values (Range)
Unit
Step
Default
Description
Scale ratio 1
0.001...1000.000
0.001
1.000
Scale ratio for analog value 1
Scale ratio 2
0.001...1000.000
0.001
1.000
Scale ratio for analog value 2
Scale ratio 3
0.001...1000.000
0.001
1.000
Scale ratio for analog value 3
Scale ratio 4
0.001...1000.000
0.001
1.000
Scale ratio for analog value 4
Section 3
1MRS758755 A
Basic functions
152
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...