Figure 138:
Functional module diagram
Level detector 1
This module compares the phase currents (RMS value) to the
Start value
setting. The
Operation mode
setting can be used to select the "Three Phase" or "Single Phase"
mode.
If in the "Three Phase" mode all the phase current values are less than the value of the
Start value
setting, the condition is detected and an enable signal is sent to the timer.
This signal is disabled after one or several phase currents have exceeded the set
Start
value
value of the element.
If in the "Single Phase" mode any of the phase current values are less than the value
of the
Start value
setting, the condition is detected and an enable signal is sent to the
timer. This signal is disabled after all the phase currents have exceeded the set
Start
value
value of the element.
The protection relay does not accept the
Start value
to be smaller than
Current block value
Level detector 2
This is a low-current detection module that monitors the de-energized condition of the
protected object. The module compares the phase currents (RMS value) to the
Start
value low
setting. If all the phase current values are less than the
Start value low
setting, a signal is sent to block the operation of the timer.
Timer
Once activated, the timer activates the
START
output and the phase-specific
ST_X
output. The time characteristic is according to DT. When the operation timer has
reached the value set by
Operate delay time
, the
OPERATE
output and the phase-
specific
OPR_X
output are activated. If the fault disappears before the module
operates, the reset timer is activated. If the reset timer reaches the value set by
Reset
delay time
, the operate timer resets and the
START
output is deactivated.
Section 4
1MRS758755 A
Protection functions
260
REC615 and RER615
Technical Manual
Summary of Contents for RELION Series
Page 1: ... RELION PRODUCT FAMILY Grid Automation REC615 and RER615 Technical Manual ...
Page 2: ......
Page 30: ...24 ...
Page 50: ...44 ...
Page 189: ...3 18 5 Settings 1MRS758755 A Section 3 Basic functions REC615 and RER615 183 Technical Manual ...
Page 206: ...200 ...
Page 514: ...508 ...
Page 714: ...708 ...
Page 786: ...780 ...
Page 796: ...790 ...
Page 798: ...792 ...
Page 803: ...797 ...