3-27
365-575-389
Installation Manual
Equipment Installation
Cabinet Installation (Continued)
Connecting the
Cabinet to
Building Ground
Introduction
The following section provides the procedures necessary to connect the cabinets
to building or office ground to:
1.
provide a direct earth ground connection for lightning protection.
2.
provide a common ground potential for electrostatic discharge (ESD)
protection.
Additional Information
All WaveStar OLS 40G and OT cabinets are shipped with ground cable
assemblies attached to the frame. It will be necessary to terminate the ground
wire in the cable rack. When a cabinet is installed, it should be connected to the
building ground as soon as possible after the cable rack is installed.
Connecting the Cabinet to Building Ground
Follow the steps listed below to connect the Cabinet to building ground:
NOTE:
The building ground cable associated with raised floor installations may be
below the floor. It is permissible to attach a ground wire nearer the base of
the frame if the contact area has been cleaned down to bare metal.
Step
Action
1
Connect the ground cable lug to the bay frame at the unpainted area in
the upper back right corner on the frame with two (2) #12-24 x 1/4
screws. (See note below for installation on raised floors.)
2
Connect the 6-gauge stranded ground wire to the building ground cable
using a crimped Thomas & Betts 54720 C-tap lug. The recommended
crimping tool is a Thomas & Betts TBM5S with die code “brown.”
Содержание WaveStar OLS 40G
Страница 4: ......
Страница 12: ...Contents xii Issue 1 0 March 2001 365 575 389 Installation Manual...
Страница 24: ...Tables xxiv Issue 1 0 March 2001 365 575 389 Installation Manual...
Страница 54: ...1 22 Issue 1 0 March 2001 365 575 389 Installation Manual Overall Installation and Test Considerations...
Страница 126: ...3 50 Issue 1 0 March 2001 365 575 389 Installation Manual Equipment Installation...
Страница 156: ...4 30 Issue 1 0 March 2001 365 575 389 Installation Manual Power Cable Installation...
Страница 228: ...5 72 Issue 1 0 March 2001 365 575 389 Installation Manual Wired Cable Installation...
Страница 366: ...7 16 Issue 1 0 March 2001 365 575 389 Installation Manual Powering...
Страница 390: ...8 24 Issue 1 0 March 2001 365 575 389 Installation Manual Network Element Startup and Provisioning...
Страница 436: ...9 46 Issue 1 0 March 2001 365 575 389 Installation Manual Local Installation Testing...
Страница 487: ...Issue 1 0 March 2001 12 15 12 Troubleshooting 12 Contents Background 2 Troubleshooting Table 3...
Страница 500: ...12 28 Issue 1 0 March 2001 365 575 389 Installation Manual Troubleshooting...
Страница 501: ...Issue 1 0 March 2001 A 1 A Releases 1 0 and2 0LBO Selection Tables A Contents Overview 2...
Страница 557: ...Issue 1 0 March 2001 F 1 F PC Setup Usage For CenterLink ManagementConsole F Contents Overview 2...
Страница 571: ...Issue 1 0 March 2001 H 1 H Optical Protection Switch OPS H Contents Overview 2...