The VOA Low Degrade alarm is raised on DWDM cards when an equipped VOA does not reach the setpoint
due to an internal problem. The alarm indicates that the attenuation has crossed the low degrade threshold.
Clear the VOA-LDEG Alarm
SUMMARY STEPS
1.
Complete the
Physically Replace a Card, on page 453
procedure for the alarmed card.
DETAILED STEPS
Complete the
Physically Replace a Card, on page 453
procedure for the alarmed card.
If the condition does not clear, log into the Technical Support Website at
http://www.cisco.com/c/en/us/support/index.html
for more information or call Cisco TAC (1 800 553-2447).
VOA-LFAIL
Default Severity: Critical (CR), Service-Affecting (SA)
Logical Objects: AOTS, OCH, OMS, OTS
The VOA Low Fail alarm is raised on DWDM cards when an equipped VOA does not reach the setpoint due
to an internal problem. The alarm indicates that the attenuation has crossed the low fail threshold. The card
must be replaced.
Clear the VOA-LFAIL Alarm
SUMMARY STEPS
1.
Complete the
Physically Replace a Card, on page 453
procedure for the alarmed card.
DETAILED STEPS
Complete the
Physically Replace a Card, on page 453
procedure for the alarmed card.
If the alarm does not get cleared, you need to report a Service-Affecting (SA) problem. Log into the Technical Support
Website at
http://www.cisco.com/c/en/us/support/index.html
for more information or log into
en/us/support/web/tsd-cisco-worldwide-contacts.html
to obtain a directory of toll-free Technical Support numbers for
your country.