Clear the TEMP-LIC Alarm
SUMMARY STEPS
1.
Procure and install a permanent license. For more information on installing a license, see the Licensing
Configuration guide.
DETAILED STEPS
Procure and install a permanent license. For more information on installing a license, see the Licensing Configuration
guide.
If the condition does not clear, log into the Technical Support Website at
http://www.cisco.com/c/en/us/support/index.html
for more information or call Cisco TAC (1 800 553-2447).
TEMP-MISM
Default Severity: Not Alarmed (NA), Non-Service-Affecting (NSA)
Logical Object: NE
Temperature Reading Mismatch Between Control Cards is raised when the temperature readings on the two
control cards are out of range of each other by more than some predefined difference (such as 5 degrees C).
A message containing power monitoring and temperature information is exchanged between the two control
cards, allowing the values to be compared. The temperature of each control card is read from a system variable.
This condition can be caused by a clogged fan filter or by fan tray stoppage.
Clear the TEMP-MISM Condition
SUMMARY STEPS
1.
Complete the
Inspect, Clean, and Replace the Reusable Air Filter, on page 457
procedure.
2.
If the condition does not clear, complete the
Remove and Reinsert a Fan-Tray Assembly, on page 460
procedure.
DETAILED STEPS
Step 1
Complete the
Inspect, Clean, and Replace the Reusable Air Filter, on page 457
procedure.
Step 2
If the condition does not clear, complete the
Remove and Reinsert a Fan-Tray Assembly, on page 460
procedure.
If the condition does not clear, log into the Technical Support Website at
http://www.cisco.com/c/en/us/support/index.html
for more information or call Cisco TAC (1 800 553-2447).
Cisco NCS 2000 series Troubleshooting Guide, Release 11.0
414
Alarm Troubleshooting
Clear the TEMP-LIC Alarm