3.23
Date Code 20171006
Instruction Manual
SEL-400 Series Relays
Basic Relay Operations
Making Simple Settings Changes
Example 3.1
Text-Edit Mode Line Editing
Set Display Point 1 through Display Point 3 to show the status of Circuit
Breaker 1, Circuit Breaker 2, and the operational state (on or off) of the
transformer cooling fans near the circuit breaker bay where you have
installed the relay. See
for information on pro-
gramming display points.
For this example, use inputs IN101, IN102, and IN105. You can use other
inputs for your particular application.
This procedure assumes that you have successfully established communica-
tion with the relay (see
Making an EIA-232 Serial Port Connection on
). In addition, you must be familiar with relay access levels and
passwords (see
Changing the Default Passwords in the Terminal on
) to change the default access level passwords.
Step 1. Prepare to control the relay at Access Level 2.
a. Using a communications terminal, type
ACC <Enter>
.
b. Type the Access Level 1 password and press
<Enter
>.
You will see the Access Level 1 => prompt.
c. Type
2AC <Enter>
.
d. Type the Access Level 2 password and press
<Enter>
.
You will see the Access Level 2 =>> prompt.
Step 2. Access the display point settings.
a. Type
SET F <Enter>
to modify the front-panel settings.
b. Advance through the front-panel settings (repeatedly type
>
and
then
<Enter>
) until you reach the
Display Points
category.
shows a representative terminal screen. The
relay displays the first line that you can edit. For the case of
display points, the line number is the display point number.
Step 3. At the Line 1 settings
?
prompt, type the following to create Dis-
play Point 1:
IN101,CB1,CLOSED,OPEN <Enter>
The relay verifies that this is a valid entry, then responds with the next
line prompt
2:
followed by the settings
?
prompt (see
).
Step 4. At the Line 2 settings
?
prompt, type the following to create Dis-
play Point 2:
IN102,CB2,CLOSED,OPEN <Enter>
The relay verifies that this is a valid entry, then responds with the next
line prompt
3:
followed by the settings
?
prompt (see
).
Step 5. At the
Display Points
prompt, use the text-edit mode line edit-
ing commands to list the active display points. Type the follow-
ing:
LIST <Enter>
After showing the active display points, the relay returns to
Line 3 followed by the settings
?
prompt.
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...