6.51
Date Code 20171021
Instruction Manual
SEL-421 Relay
Protection Applications Examples
500 kV Parallel Transmission Lines With Mutual Coupling Example
Phase Instantaneous Overcurrent Pickup (Group)
50P1P
Level 1 Pickup (OFF, 0.25–100 A secondary)
7.21
Phase Overcurrent Definite-Time Delay (Group)
67P1D
Level 1 Time Delay (0.000–16000 cycles)
0.000
Phase Overcurrent Torque Control (Group)
67P1TC
Level 1 Torque Control (SEL
OGIC
Equation)
1
Selectable Operating Quantity Inverse-Time Overcurrent Element 1 (Group)
51S1O
51S1 Operating Quantity (IA
n
, IB
n
, IC
n
, IMAX
n
,
I1L, 3I2L, 3I0
n
)
a
3I0L
51S1P
51S1 Overcurrent Pickup (0.25–16 A secondary)
0.50
51S1C
51S1 Inverse-Time Overcurrent Curve (U1–U5)
U3
51S1TD
51S1 Inverse-Time Overcurrent Time Dial (0.50–15) 1.68
51S1RS
51S1 Inverse-Time Overcurrent Electromechanical
Reset (Y, N)
Y
51S1TC
51S1 Torque Control (SEL
OGIC
Equation)
32GF
Zone/Level Direction (Group)
DIR3
Zone/Level 3 Direction Control (F, R)
R
Directional Control (Group)
ORDER
Ground Directional Element Priority
(combine Q, V, I)
QV
E32IV
Zero-Sequence Voltage And Current Enable
(SEL
OGIC
Equation)
1
Pole-Open Detection (Group)
EPO
Pole-Open Detection (52, V)
52
SPOD
Single-Pole Open Dropout Delay (cycles)
0.500
3POD
Three-Pole Open Dropout Delay (cycles)
0.500
POTT Trip Scheme (Group)
Z3RBD
Zone 3 Reverse Block Time Delay (0.000–16000
cycles)
5.000
EBLKD
Echo Block Time Delay (OFF, 0.000–16000 cycles)
10.000
ETDPU
Echo Time Delay Pickup (OFF, 0.000–16000 cycles) 2.000
EDURD
Echo Duration Time Delay (0.000–16000 cycles)
4.000
EWFC
Weak Infeed Trip (Y, N, SP)
N
27PWI
Weak Infeed Phase Undervoltage Pickup
(1.0–200 V secondary)
47.0
27PPW
Weak Infeed Phase-to-Phase Undervoltage Pickup
(1.0–300 V secondary)
80.0
59NW
Weak Infeed Zero-Sequence Overvoltage Pickup
(1.0–200 V secondary)
5.0
PT1
General Permissive Trip Received
(SEL
OGIC
Equation)
RMB1A
PT3
Three-Pole Permissive Trip Received
(SEL
OGIC
Equation)
RMB2A
Table 6.13
Settings for 500 kV Parallel TX Example (Sheet 5 of 7)
Setting
Prompt
Entry
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...