![Schweitzer Engineering Laboratories SEL-421-4 Instruction Manual Download Page 452](http://html.mh-extra.com/html/schweitzer-engineering-laboratories/sel-421-4/sel-421-4_instruction-manual_1216726452.webp)
6.116
SEL-421 Relay
Instruction Manual
Date Code 20171021
Protection Applications Examples
EHV Parallel 230 kV Underground Cables Example
ESERCMP
Series-Compensated Line Logic (Y, N)
N
ECDTD
Distance Element Common Time Delay (Y, N)
Y
ESOTF
Switch-Onto-Fault (Y, N)
Y
EOOS
Out-of-Step (Y, Y1, N)
N
ELOAD
Load Encroachment (Y, N)
N
E50P
Phase Inst./Def.-Time O/C Elements (N, 1–4)
1
E50G
Res. Ground Inst./Def. Time O/C Elements
(N, 1–4)
N
E50Q
Negative-Sequence Inst./Def. Time O/C Elements
(N, 1–4)
3
E51S
Selectable Inverse Time O/C Element (N, 1–3)
1
E32
Directional Control (Y, AUTO, AUTO2)
AUTO2
ECOMM
Comm.-Assisted Tripping (N, DCB, POTT,
POTT2, POTT3, DCUB1, DCUB2)
POTT
EBFL1
Breaker 1 Failure Logic (N, 1, 2, Y1, Y2)
N
E25BK1
Synchronism Check for Breaker 1 (Y, N, Y1, Y2)
N
E79
Reclosing (Y, Y1, N)
N
EMANCL
Manual Closing (Y, N)
N
ELOP
Loss-of-Potential (Y, Y1, N)
Y1
EDEM
Demand Metering (N, THM, ROL)
N
EADVS
Advanced Settings (Y, N)
Y
Mho Phase-Distance Element Reach (Group)
Z1MP
Zone 1 Reach (OFF, 0.05–64
secondary)
0.38
Z2MP
Zone 2 Reach (OFF, 0.05–64
secondary)
0.58
Z3MP
Zone 3 Reach (OFF, 0.05–64
secondary)
0.58
Mho Phase-Distance Element Time Delay (Group)
Z1PD
Zone 1 Time Delay (OFF, 0.000–16000 cycles)
OFF
Z2PD
Zone 2 Time Delay (OFF, 0.000–16000 cycles)
OFF
Z3PD
Zone 3 Time Delay (OFF, 0.000–16000 cycles)
OFF
Quadrilateral Ground-Distance Element Reach (Group)
XG1
Zone 1 Reactance (OFF, 0.05–64
secondary)
0.38
RG1
Zone 1 Resistance (0.05–50
secondary)
1.29
XG2
Zone 2 Reactance (OFF, 0.05–64
secondary)
0.58
RG2
Zone 2 Resistance (0.05–50
secondary)
1.97
XG3
Zone 3 Reactance (OFF, 0.05–64
secondary)
0.58
RG3
Zone 3 Resistance (0.05–50
secondary)
2.46
XGPOL
Quad Ground Polarizing Quantity (I2, IG)
I2
TANGG
Nonhomogeneous Correction Angle
(–40.0 to +40 degrees)
–2.2
Zero-Sequence Current Compensation Factor (Group)
k0M1
Zone 1 ZSC Factor Magnitude (AUTO, 0.000–10)
0.385
k0A1
Zone 1 ZSC Factor Angle (–180.0 to +180 degrees) –46.7
Table 6.31
Settings for 230 kV Parallel Cables Example (Sheet 2 of 5)
Setting
Prompt
Entry
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...