Date Code 20171006
Instruction Manual
SEL-400 Series Relays
Instruction Manual
A P P E N D I X
C
Cybersecurity Features
The SEL-400 series relays have a number of security features to assist users with
meeting their cybersecurity design requirements.
Ports and Services
Physical Ports
SEL-400 series relays include four serial ports and as many as four Ethernet
ports. Each physical serial port and Ethernet port can be individually disabled
using the EPORT setting. By default, all of the ports are enabled.
SEL recommends that unused communications ports be disabled.
SEL-400 series relays with a TiDL configuration also have eight EtherCAT ports.
These are always enabled, but they have a very limited functionality, as described
below.
IP Ports
When using Ethernet, there are a number of possible IP ports available within the
relay. Many of these IP port numbers are configurable. All IP ports can be dis-
abled and are disabled by default.
describes each of these.
Note that IP traffic is only supported on station bus ports, so process bus ports
have no open IP ports. See
Ethernet Communications on page 15.6
for more infor-
mation on these settings.
Table C.1
IP Port Numbers
IP Port
Default
Port
Selection
Setting
Network
Protocol
Default Port
State
Port Enable
Setting
Purpose
21
--
TCP
Disabled
FTPSERV
FTP protocol access for file transfer of settings and reports
23
TPORT
TCP
Disabled
ETELNET
Telnet access for general engineering terminal access
80
HTTPPOR
TCP
Disabled
EHTTP
Web server access to read various relay information
102
--
TCP
Disabled
E61850
IEC 61850 MMS for SCADA functionality
123
SNTPPOR
UDP
Disabled
ESNTP
SNTP time synchronization
319/320
--
UDP
Disabled
EPTP
PTP time synchronization
4712/ 4713
PMOTCP1/
PMOUDP1
TCP/UDP
Disabled
PMOTS1
Synchrophasor data output, session 1
4712/ 4713
PMOTCP2/
PMOUDP2
TCP/UDP
Disabled
PMOTS2
Synchrophasor data output, session 2
20000
DNPPNUM
TCP/UDP
Disabled
EDNP
DNP3 for SCADA functionality
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...