4.13
Date Code 20171006
Instruction Manual
SEL-400 Series Relays
Front-Panel Operations
Front-Panel Layout
3:
0
4:
0,“Circuit BK1 SF6 Gas”
5:
IN109,,“ --Alarm--”,“ --Normal--”
6:
1
7:
1,“Circuit Breaker 2”
8:
B2IAFIM,“ A PH=(6.1,1) A pri”
9:
IN109,, “SF6 ALARM”, D
Fixed text is set by assigning an alias to a “1” or “0.” Blank lines are set by
assigning a blank alias to a “1” or “0.” The circuit breaker closed condition is
indicated by the set state, “--Closed--” where leading spaces are added to
center the set state message. Add a clear state named “--Open--” to show that
the circuit breaker is open. The circuit breaker alarm condition is indicated
by the set state, “--Alarm--” where leading spaces are added to center the set
state message. Add a clear state named “--Normal--” to show that the circuit
breaker is not in alarm. User text “A PH=” and “A pri” allows for customized
display of the Circuit Breaker 2 A-Phase current, which has been formatted
to display numerically as XXXX.X. Double font display is used to give
greater visibility to the SF6 Alarm. A horizontal scroll appears while in man-
ual-scrolling mode regardless of whether or not the display point label width
requires two full screens to display.
Example 4.3
Monitoring Test Modes With Display Points
This example uses the Relay Word bit TESTFM (Fast Meter test running) to
activate a front-panel display point that alerts an onsite operator that the
relay is in Fast Meter test mode.
In the Front Panel settings (
SET F
), enter the following after the Line 10
prompt:
10:
TESTFM,,“FAST METER TEST!!!!”
The LCD displays the screen shown in
as a part of the
ROTATING
DISPLAY
if the Fast Meter test is running. (Instruct the operator to view the
relay front panel for messages or warnings as the last item on a “Leaving the
Substation” checklist.)
Again, this display point application example does not require a clear state,
so the clear state is blank. If the Fast Meter test is not running and no other
display points are active, the relay shows a blank screen in the
ROTATING
DISPLAY
.
Example 4.2
Creating a Display Point (Continued)
Figure 4.13
Fast Meter Display Points Sample Screen
FAST METER TEST!!!!
ROTATING DISPLAY
Press for menu
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...