6.101
Date Code 20171021
Instruction Manual
SEL-421 Relay
Protection Applications Examples
EHV Parallel 230 kV Underground Cables Example
show that the XAG calculation overreaches by 6.2 per-
cent (i.e., 100% – 93.8% = 6.2%) if the sheath is the return path for the ground
fault; therefore, you should not set k01 based on the sheath and ground (parallel)
return path.
Sheath Return Path
lists the corresponding XAG (reactance of the phase-to-ground fault)
calculations for the remote single phase-to-ground fault for each of the three pos-
sible zero-sequence cable impedances when the k01 calculation is based on the
sheath return path.
show that there is no Zone 1 ground-distance overreach.
Therefore, set k01 based on Z
0L1(sheath)
.
k0M1 :=
0.385
.
Zone 1 ZSC Factor Magnitude (AUTO, 0.000–10)
k0A1 :=
–46.7
.
Zone 1 ZSC Factor Angle (–180.0 to +180.0 degrees)
k0 and k0R
Set the forward (k0) and reverse (k0R) zero-sequence current compensation fac-
tors so that the overreaching zones of ground-distance protection do not under-
reach for any internal ground fault. Put both parallel cables in service.
lists the corresponding XAG calculations for a remote (Station R) ground fault
for each of the three possible zero-sequence cable impedances when the k0 calcu-
lation is based on Z
0L1(ground)
. (Replace k01 with k0 or replace k01 with k0R in
.)
show that the XAG calculation does not underreach
when you set k0 based on the ground return path. Set k0 and k0R based on
Z
0L1(ground)
.
Table 6.26
XAG Measurement for Remote AG Fault (k01 = 0.374
–39.2°,
Sheath and Ground Return Path)
Calculation
Z0L1(sheath)
Z0L1(ground)
Z0L1(sheath and ground)
XAG (secondary ohms)
0.45
3.04
0.48
Overreach/Underreach
a
a
O indicates overreach, U indicates underreach.
93.8% (O)
633% (U)
100%
Table 6.27
XAG Measurement for Remote AG Fault (k01 = 0.385
–46.7°,
Sheath Return Path)
Calculation
Z0L1(sheath)
Z0L1(ground)
Z0L1(sheath and ground)
XAG (secondary ohms)
0.48
3.17
0.51
Overreach/Underreach
a
a
O indicates overreach, U indicates underreach.
100%
660% (U)
106% (U)
Table 6.28
XAG Measurement for Remote AG Fault (k0 = 6.105
44.5°, Ground
Return Path)
Calculation
Z0L1(sheath)
Z0L1(ground)
Z0L1(sheath and ground)
XAG (secondary ohms)
0.04
0.48
0.05
Overreach/Underreach
a
a
O indicates overreach, U indicates underreach
8.33% (O)
100%
10.4% (O)
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...