14.46
SEL-400 Series Relays
Instruction Manual
Date Code 20171006
ASCII Command Reference
Command Description
If the circuit breaker control enable jumper BREAKER is not in place, the relay
aborts the command and responds,
Aborted: the breaker jumper is not
installed
.
When you issue the
PUL
command and the breaker jumper is in place, the relay
responds,
Pulse contact OUTnnn for s seconds (Y/N)?.
If you answer
Y <Enter>
, the relay asserts OUT
nnn
for the time you specify.
During the
PUL
operation, the Relay Word bit corresponding to the control out-
put you specified (OUT
nnn
) asserts; Relay Word bit TESTPUL also asserts
during any
PUL
command, so you can monitor pulse operation by programming
TESTPUL into event triggers and alarm outputs.
QUIT
Use the
QUIT
command to revert to Access Level 0 (exit relay control).
Access Level 0 is the lowest access level; the relay performs no password check
to descend to this level (or remain at this level).
In a Telnet session,
QUIT
terminates the connection.
RTC
Use the
RTC
command to display a description of all data being received on syn-
chrophasor client channels. This report will list the analog quantity and Relay
Word bits the data gets stored in locally, matched up with a label provided by the
sending PMU. Use this information as aid to understanding the local values.
NOTE:
Not all SEL-400 series relays
support synchrophasors.
SER
The
SER
command retrieves SER records. The relay SER captures state changes
of Relay Word bit elements and relay conditions. Relay conditions include
startup, relay enable/disable, group changes, settings changes, memory queue
overflow, and SER autoremoval/reinsertion. For more information on the SER,
see
Sequential Events Recorder (SER) on page 9.28
Table 14.105
QUIT Command
Command
Description
Access Level
QUIT
Go to Access Level 0 (exit relay control).
0, 1, B, P, A, O, 2
Table 14.106
RTC Command
Command
Description
Access Level
RTC
Display report of all configured synchrophasor client
data labels.
1, B, P, A, O, 2
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...