14.41
Date Code 20171006
Instruction Manual
SEL-400 Series Relays
ASCII Command Reference
Command Description
MET RTC
Use the
MET RTC
command to view the data received on all active synchropha-
sor client channels.
MET T
Use the
MET T
command to view the temperature data from the SEL-2600A
RTD Module. This command requires setting PROTO = RTD for the serial port
connected to the SEL-2600A RTD Module.
NOTE:
Some SEL-400 series relays
use the option MET RTD to get this
same information.
NOTE:
The SEL-487B does not
support RTD inputs.
The relay displays the number of RTD channels specified by the RTDNUM Port
Setting. If the RTD protocol is not enabled on any of the relay ports, the relay dis-
plays the following:
No data available
If there is a communications failure between the relay and the SEL-2600A, as
indicated by the RTDCOMF Relay Word bit, the relay displays the following:
Communication Failure
If the RTDFL Relay Word bit is set to indicate a SEL-2600A failure, the relay
displays the following:
SEL-2600 Failure
If any of the RTD
x
TY Port Settings are set to NA, the relay displays the follow-
ing for that channel:
Channel Not Used
If the RTD
xx
ST Relay Word bit is set for any of the RTDNUM channels being
reported, the relay displays the following:
Channel Failure
OACCESS
Use the
OACCESS
command to gain access to Access Level O (output). See
Access Levels and Passwords on page 3.7
for more information.
Table 14.93
MET RTC Command
Command
Description
Access Level
MET RTC
Display received synchrophasor client data
1, B, P, A, O, 2
MET RTC
k
Display received synchrophasor client data
k
times
1, B, P, A, O, 2
Table 14.94
MET T Command
Command
Description
Access Level
MET T
Display as many as 12 temperature analog values from
the SEL-2600A RTD Module.
1, B, P, A, O, 2
MET T
k
Display as many as 12 temperature analog values from
the SEL-2600A RTD Module successively for
k
times.
1, B, P, A, O, 2
Table 14.95
OAC Command
Command
Description
Access Level
OAC
Go to Access Level O (output).
1, B, P, A, O, 2
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...