17.7
Date Code 20171006
Instruction Manual
SEL-400 Series Relays
IEC 61850 Communication
IEC 61850 Operation
are also mapped to internal commands, read and write actions and MMS infor-
mation report messages. In the case of an unsuccessful control request, the relay
will send the appropriate response PDU indicating that there was a problem and
an MMS information report that contains more detailed information about the
problem that occurred.
When writing controls, the client must select and write the entire Oper, SBOw or
Cancel structure to the relay. See
for the attributes of the CON Logi-
cal Device and ST and CO functional constraints (FC) of LN RBGGIO1 used for
controls of RB01 through RB08.
Control Error Messages
If a control request results in an error condition, the relay will respond with an
AddCause value in an MMS information report. See Clause 20.5.2.9 of
IEC 61850-7-2 for additional information on the AddCause values.
SEL-400 series relays support the AddCause values in
as part of the
LastApplError information report.
Figure 17.1
MMS Client View of the CON Logical Device
Table 17.4
AddCause Descriptions (Sheet 1 of 2)
AddCause
Enumeration
AddCause
Description
Error Condition
0
Unknown
No other AddCause value defined within this
section applies
2
Blocked-by-switch-
ing-hierarchy
Logical node is set to local mode, i.e. Loc.stVal = true
3
Select-failed
Originator category not allowed to issue control com-
mands or SelectWithValue operation fails
4
Invalid-position
For controls with enhanced security, an AddCause of
“Invalid-position” (4) will be sent if the control status
changes to an unexpected value. If no control status
change is detected after the operate time-out period, an
AddCause of “Time-limit-over” (16) will be sent.
5
Position-reached
Control status is already at the desired state
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...