9.12
SEL-400 Series Relays
Instruction Manual
Date Code 20171006
Reporting
Oscillography
The configuration file has the following format:
➤
Station name, device identification, COMTRADE standard year
➤
Number and type of channels
➤
Channel name units and conversion factors
➤
Line frequency
➤
Sample rate and number of samples
➤
Date and time of first data point
➤
Date and time of trigger point
➤
Data file type
➤
Time stamp multiplication factor
.DAT File
NOTE:
The analog data are time-
aligned to when the data changed on
the input terminals. Similarly, the
contact inputs are time-aligned to
when the data changed on the input
terminals. All other digital data are
time-aligned to when the value
changed in the relay.
The .DAT file follows the COMTRADE binary standard. The format of the binary
data files is sample number, time stamp, data value for each analog channel, and
grouped status channel data for each sample in the file. There are no data separa-
tors in the binary file, and the file contains no carriage return/line feed characters.
The sequential position of the data in the binary file determines the data transla-
tion. Refer to the IEEE Std C37.111-1999, Common Format for Transient Data
Exchange (COMTRADE) for Power Systems for more information. Programs
that read the binary COMTRADE files include
AC
SEL
ERATOR
Analytic Assis-
tant SEL-5601 Software and
AC
SEL
ERATOR
QuickSet SEL-5030 Software.
1,87USAFE,,,0
2,UNUSED2,,,0
3,UNUSED3,,,0
4,UNUSED4,,,0
5,OC1,,,0
6,CC1,,,0
7,OC2,,,0
8,CC2,,,0
9,87LA,,,0
10,87LB,,,0
11,87LC,,,0
12,87LQ,,,0
13,87LG,,,0
14,87FLSOK,,,0
15,87DTTRX,,,0
.
.
.
382,PCT06Q,,,0
383,PCT07Q,,,0
384,PCT08Q,,,0
384 Digital Points
60
Nominal System Frequency (INFREQ Setting)
1
2000,1000
2000 = Sample Rate (SRATE setting)
1000 = Length of the Report x Sample Rate (LER x SRATE)
17/03/2011,08:36:38.697687
Time Stamp of the First Data Point
17/03/2011,08:36:38.799850
Time Stamp of the Trigger Point
BINARY
1
a
If ERDIG is set to S, the digital points are all the Relay Word bits set in ERDG as well as the Relay Word bits that are always included in the
event report. If ERDIG is set to A, the digital points are all the Relay Word bits in the device.
COMTRADE .CFG Configuration File Data (Continued)
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...