6.94
SEL-421 Relay
Instruction Manual
Date Code 20171021
Protection Applications Examples
EHV Parallel 230 kV Underground Cables Example
Set Zone 1 phase-distance protection to 80 percent of the cable positive-sequence
impedance.
Z1MP = 0.8 • Z
1L1
= 0.8 • 0.48
= 0.38
Z1MP :=
0.38
.
Zone 1 Reach (OFF, 0.05–64
secondary)
Zone 2 Phase-Distance Element Reach
Zone 2 phase-distance protection must have adequate reach to detect all phase-to-
phase, phase-to-phase-to-ground, and three-phase faults along the protected
cable. Set Zone 2 phase-distance protection to 120 percent of the cable positive-
sequence impedance. With this reach, high-speed tripping occurs via the commu-
nications channel for faults located in the last 20 percent of the cable.
Z2MP = 1.2 • Z
1L1
= 1.2 • 0.48
= 0.58
Z2MP :=
0.58
.
Zone 2 Reach (OFF, 0.05–64
secondary)
Zone 3 Phase-Distance Element Reach
Zone 3 phase-distance protection must have adequate reach to prevent unwanted
tripping during current reversals when the parallel line is in service because this
example uses a POTT scheme. So that Zone 3 has greater fault coverage than
Zone 2 at the remote terminal, set the reach to remote Zone 2 and rely upon the
length of the protected cable as the safety margin.
Z3MP = Z2P = 0.58
Z3MP :=
0.58
.
Zone 3 Reach (OFF, 0.05–64
secondary)
Ground-Distance Elements (21XG)
Quadrilateral Ground-Distance Element Reach
The main advantage of ground-distance protection is that Zone 1 provides instan-
taneous protection independent of the communications channel. Typically cable
faults have little fault resistance; it is advantageous to conservatively set the resis-
tance reach for quadrilateral ground-distance protection. Supplement quadrilat-
eral ground-distance protection with directional negative-sequence overcurrent
elements. The directional negative-sequence overcurrent elements employed in
the communications-assisted tripping scheme provide excellent resistive cover-
age for high-resistance ground faults (e.g., a contaminated pothead flashes over).
The reactive reach for each zone of quadrilateral ground-distance protection lies
on the relay characteristic angle (Z1ANG), rather than on the ordinate (reactance)
of the impedance plane (see
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...