8.29
Date Code 20171021
Instruction Manual
SEL-421 Relay
Settings
Group Settings
Make
settings if Group settings E25BK1 := Y or E25BK2 := Y.
Make
settings if Group setting E25BK1 := Y.
NOTE:
If the relay is using a remote
data acquisition system, such as TiDL,
the operating times will be delayed by
1.5 ms. Use caution when setting the
relay for synchronism check to
account for this added delay
Make
settings if Group setting E25BK2 := Y.
FOPU1
Flashover Time Delay—BK1 (0.000–6000 cycles)
9.000
9.000
0.125
BLKFOA1
Block A-Phase Flashover—BK1 (SEL
OGIC
Equation)
NA
NA
BLKFOB1
Block B-Phase Flashover—BK1 (SEL
OGIC
Equation)
NA
NA
BLKFOC1
Block C-Phase Flashover—BK1 (SEL
OGIC
Equation)
NA
NA
BFTR1
Breaker Failure Trip—BK1 (SEL
OGIC
Equation)
NA
NA
BFULTR1
Breaker Failure Unlatch Trip—BK1 (SEL
OGIC
Equation)
NA
NA
a
Replace 1 with 2 in the setting for Breaker 2.
b
Setting only available when EBFL1 := 2, Y2 or EBFL2 := 2, Y2.
Table 8.70
Breaker 1 Failure Logic (and Breaker 2 Failure Logic
a
) (Sheet 2 of 2)
Setting
Prompt
Default Value
Increment
5 A
1 A
Table 8.71
Synchronism-Check Element Reference
Setting
Prompt
Default
Value
Increment
SYNCP
Synchronism Reference (VAY, VBY, VCY, VAZ, VBZ,
VCZ)
VAY
25VL
Voltage Window Low Threshold (20.0–200 V secondary)
55.0
0.1
25VH
Voltage Window High Threshold (20.0–200 V secondary)
70.0
0.1
Table 8.72
Breaker 1 Synchronism Check
Setting
Prompt
Default
Value
Increment
SYNCS1
Synchronism Source 1 (VAY, VBY, VCY, VAZ, VBZ,
VCZ)
VAZ
KS1M
Synchronism Source 1 Ratio Factor (0.10–3)
1.00
0.01
KS1A
Synchronism Source 1 Angle Shift (0, 30, 60, 90, 120,
150, 180, 210, 240, 270, 300, 330 degrees)
0
30
25SFBK1
Maximum Slip Frequency—BK1 (OFF, 0.005–0.5 Hz)
0.050
0.001
ANG1BK1 Maximum Angle Difference 1—BK1 (3.0–80 degrees)
10.0
0.1
ANG2BK1 Maximum Angle Difference 2—BK1 (3.0–80 degrees)
10.0
0.1
TCLSBK1
Breaker 1 Close Time (1.00–30 cycles)
a
a
Adjust setting TCLSBK1 in 0.25-cycle steps.
8.00
0.25
BSYNBK1 Block Synchronism Check—BK1(SEL
OGIC
Equation)
NA
Table 8.73
Breaker 2 Synchronism Check (Sheet 1 of 2)
Setting
Prompt
Default
Value
Increment
SYNCS2
Synchronism Source 2 (VAY, VBY, VCY, VAZ, VBZ,
VCZ)
VBZ
KS2M
Synchronism Source 2 Ratio Factor (0.10–3)
1.00
0.01
KS2A
Synchronism Source 2 Angle Shift (0, 30, 60, 90, 120,
150, 180, 210, 240, 270, 300, 330 degrees)
0
30
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...