5.31
Date Code 20171006
Instruction Manual
SEL-400 Series Relays
Control
QuickSet Bay Control Screens
89ALP01
This timer counts down when both 89AM01 and 89BM01 are in the same state
(both asserted or both deasserted). When this disconnect alarm timer expires, an
alarm condition exists and the 89AL01 Relay Word bit asserts.
Set the 89ALP01 timer longer than the expected operation (undetermined state)
time, but less than the 89CST01 or 89OST01 seal-in timers.
89CCN01, 89OCN01
These SEL
OGIC
control equations close or open Disconnect 1. Take care when
programming these equations, because there is no breaker jumper supervision or
access level safeguard in place for this disconnect operate method. These settings
only work when the LOCAL Relay Word bit is deasserted.
89CST01, 89OST01
These seal-in timers are intended to keep the close or open signal asserted long
enough to allow the Disconnect 1 operation to complete. Set the seal-in timers 10
to 15 percent longer than the expected disconnect operate time to give the discon-
nect switch time to complete the operation.
Cold weather and low battery voltages can impact disconnect switch operation
times. Be sure to consider these conditions when setting the seal-in timers.
89CIT01, 89OIT01
The close/open Disconnect 1 immobility timers are triggered at the same time as
the seal-in timers. Expiration of these immobility timers indicates that the Dis-
connect 1 auxiliary contact status failed to change state within the expected time
frame.
Set the immobility timers longer than the expected time for the disconnect to
leave the initial state (as reported by the 89AM01 and 89BM01 Relay Word bits),
but less than the seal-in timer.
Cold weather and low battery voltages can impact disconnect switch operation
times. Be sure to consider these conditions when setting the immobility timers.
89CRS01, 89ORS01
These settings reset the seal-in circuit when either the seal-in timer expires or the
intended open/close status signal asserts. This is intended to stop driving the Dis-
connect 1 motor to close or open when the desired state has been reached.
89CBL01, 89OBL01
These SEL
OGIC
control equations provide an optional custom method for block-
ing all means of close/open control for Disconnect 1.
89CIR01, 89OIR01
These SEL
OGIC
control equations reset the Disconnect 1 close/open immobility
timers.
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...