![Schweitzer Engineering Laboratories SEL-421-4 Instruction Manual Download Page 1239](http://html.mh-extra.com/html/schweitzer-engineering-laboratories/sel-421-4/sel-421-4_instruction-manual_12167261239.webp)
14.33
Date Code 20171006
Instruction Manual
SEL-400 Series Relays
ASCII Command Reference
Command Description
HIS CA and HIS RA
The
HIS CA
and
HIS RA
commands clear all history data and event reports
from memory. Use these commands to completely delete high-resolution/event
report data captures.
If you issue the
HIS CA
and
HIS RA
commands, the relay prompts you with
Are
you sure (Y/N)?.
If you answer
Y <Enter>
, the relay clears all history data and
event reports. The relay resets the event report number to 10000.
ID
Use the
ID
command to extract relay identification codes.
Each line of the
ID
command report contains an identification code and a line
checksum. The relay presents these codes in the following order:
FID: the Firmware Identification string
BFID: the Boot Firmware Identification string
CID: the checksum of the firmware
DEVID: the RID string as stored in the relay settings of the IED
DEVCODE: a unique Device Code (for Modbus identification purposes)
PARTNO: the Part Number
SERIALNO: the serial number of the relay
CONFIG: abcdef
The designator positions indicate a specific relay configuration:
“a” represents the nominal frequency, where 0 = N/A, 1 = 60 Hz, and
2 = 50 Hz.
“b” represents the phase rotation, where 0 = N/A, 1 = ABC, and 2 = ACB.
“c” represents the phase input current scaling, where 0 = N/A, 1 = 5 A,
and 2 = 1 A.
“d” represents the neutral input current scaling, where 0 = N/A, 1 = 5 A,
2 = 1 A.
“e” represents the voltage input connection, where 0 = N/A, 1 = Delta,
and 2 = Wye.
“f” represents the current input connection, where 0 = N/A, 1 = Delta, and
2 = Wye.
SPECIAL: the Special Configuration Designators—a mechanism for antici-
pating future product enhancements
Table 14.77
HIS CA and HIS RA Commands
Command
Description
Access Level
HIS CA
Clear all event data for all ports.
P, A, O, 2
HIS RA
Clear all event data for all ports.
P, A, O, 2
Table 14.78
ID Command
Command
Description
Access Level
ID
Return a list of relay identification codes.
0, 1, B, P, A, O, 2
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...