12.24
SEL-400 Series Relays
Instruction Manual
Date Code 20171006
Settings
Notes Settings
The Event Report Analog Quantities category is a freeform category in which
you can select as many as 20 analog quantities to report in the relay event reports.
By default, no analog quantities are configured.
The Event Reporting Digital Elements category is a freeform settings area in
which as many as 800 relay words from as many as 100 relay word bit rows may
be selected. See the product-specific instruction manual for the default configura-
tion. The 100 row limit includes the base set of Relay Word bits always included
in oscillography and event reports as described in
Section 7: Metering, Monitor-
ing, and Reporting
in the product-specific instruction manual.
Notes Settings
Avoid losing important information about the relay. Use the Notes settings like a
text pad to leave notes about the relay in the Notes area of the relay. Notes entries
are in a single block of 100 lines. By default, there is no text stored in the Notes set-
tings.
Table 12.40
Signal Profile
Label
Prompt
Default Value
SPAR
Signal Profile Acq. Rate (1,5,15,30,60 min)
5
SPEN
Signal Profile Enable (SEL
OGIC
Eqn.)
0
Table 12.41
Event Reporting
Label
Prompt
Default Value
ERDIG
Store Selected (S) or All (A) Relay Word Bits
S
SRATE
Sample Rate of Event Report (1, 2, 4, 8 kHz)
2
LER
a
a
The upper end of the range is reduced by a factor of 4 if ERDIG is set to A.
Length of Event Report (0.25–3.00 seconds); SRATE := 8
0.50
PRE
b
b
The upper limit for PRE is the set LER minus 0.05 s.
Length of Pre-Fault (0.05–0.25 seconds); SRATE := 8
0.10
LER
Length of Event Report (0.25–6.00 seconds); SRATE := 4
0.50
PRE
Length of Pre-Fault (0.05–0.25 seconds); SRATE := 4
0.10
LER
Length of Event Report (0.25–12.00
c
seconds); SRATE := 2
c
In the SEL-411L, the upper bound is 9.00 s.
0.50
PRE
Length of Pre-Fault (0.05–0.25 seconds); SRATE := 2
0.10
LER
Length of Event Report (0.25–24.00
d
seconds); SRATE := 1
d
In the SEL-411L, the upper bound is 12.00 s.
0.50
PRE
Length of Pre-Fault (0.05–0.25 seconds); SRATE := 1
0.10
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...