3.46
SEL-400 Series Relays
Instruction Manual
Date Code 20171006
Basic Relay Operations
Examining Relay Elements
Step 6. Connect a test source to the relay.
a. Set the current output of a test source to zero output level.
b. Connect a single-phase current output of the test source to the
IAW analog input.
Step 7. View the target status change.
a. Increase the current source to produce a current magnitude
greater than 15.00 A secondary in the relay.
b. Observe the 50P1 target on the front-panel display.
You will see the 50P1 element status change to 1 when the input
current exceeds the 50P1P setting threshold.
Step 8. Press
ESC
to return to the
MAIN MENU
.
View Relay Elements Using the Front-Panel LED
The procedure in the following steps shows you how to use a front-panel LED to
view a change-in-state for the SEL-451 50P1 Phase-Instantaneous Overcurrent
element.
In this example, use QuickSet to configure the relay. You must have a computer
that is communicating with the relay and running QuickSet (see
Changes in Initial Global Settings on page 3.20
). In addition, you need a variable
current source suitable for relay testing.
Step 1. Prepare to control the relay with QuickSet by establishing communi-
cation, checking passwords, and reading relay settings.
Step 2. Set a pushbutton LED SEL
OGIC
control equation.
a. Expand the
Front Panel
branch of the
Settings
tree view and
click
Pushbuttons
(see
).
QuickSet displays the
Pushbuttons
dialog box similar to that
b. Click in the
PB6_LED
text box and type
50P1
.
c. Tab or click to any other text box.
QuickSet checks the validity of the setting.
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...