7.2
SEL-421 Relay
Instruction Manual
Date Code 20171021
Metering, Monitoring, and Reporting
Metering
Breaker 1 or Circuit Breaker 2 by entering
MET BK1
or
MET BK2
, respec-
tively. Additionally, the
MET PM
command provides time-synchronized phasor
measurements at a specific time, e.g.,
MET PM 12:00:00
.
lists
MET
command variants for instantaneous, maximum/minimum,
demand, and energy metering. See
METER on page 14.37 in the SEL-400 Series
Relays Instruction Manual
and
in this manual for more
information on these and other
MET
command options. Other
MET
command
options are for viewing protection and automation variables, analog values from
M
IRRORED
B
ITS
communications, and synchronism check.
Instantaneous Metering
Use instantaneous metering to monitor power system parameters in real time.
The SEL-421 provides these fundamental frequency readings:
➤
Fundamental frequency phase voltages and currents
➤
Phase-to-phase voltages
➤
Sequence voltages and currents
➤
Fundamental real, reactive, and apparent power
➤
Displacement power factor
You can also monitor these real-time rms quantities (with harmonics included):
➤
RMS phase voltages and currents
➤
Real and apparent rms power
➤
True power factor
Both the fundamental and the rms-metered quantities are available for the LINE
input. The relay also provides both the fundamental and rms circuit breaker cur-
rents for circuit breakers BK1 and BK2.
Table 7.1
MET Command
Name
a
a
n
is 1 or 2, representing Circuit Breaker 1 and Circuit Breaker 2, respectively.
Description
MET
Display Fundamental Line metering information
MET BK
n
Display Fundamental Circuit Breaker
n
metering information
MET RMS
Display rms Line metering information
MET BK
n
RMS
Display rms Circuit Breaker
n
metering information
MET M
Display Line Maximum/Minimum metering information
MET BK
n
M
Display Circuit Breaker
n
Maximum/Minimum metering information
MET RM
Reset Line Maximum/Minimum metering information
MET BK
n
RM
Reset Circuit Breaker
n
Maximum/Minimum metering information
MET D
Display Demand Line metering information
MET RD
Reset Demand Line metering information
MET RP
Reset Peak Demand Line metering information
MET E
Display Energy Line metering information
MET RE
Reset Energy Line metering information
MET SYN
Display Synchronism Check voltage and slip angle/frequency information
MET BAT
Display DC Battery Monitor information
MET PM
Display Phasor Measurement (Synchrophasor) metering information
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...