6.179
Date Code 20171021
Instruction Manual
SEL-421 Relay
Protection Applications Examples
230 kV Tapped Transmission Line Application Example
Control Inputs
Connect the relay control inputs as specified in
. This table shows the
substation equipment that each control input monitors.
Control Outputs
59: ###
60: ### SET CONDITIONING TIMER 1
61: ### SUPERVISES BK1 RECLOSING, ASSERTS IF MOD IS CLOSED AND IN SYNC. OR
62: ### MOD LATCH SET AND MOD OPEN AND BK1 BUS HOT FOR FOUR SECONDS
63: PCT01PU := 240.00 # FOUR SECOND PICKUP TIME
64: PCT01DO := 0.0 # NO DELAY ON DROPOUT
65: PCT01IN := NOT IN103 AND 25A1BK1 OR PLT01 AND IN103 AND 59VS1
66: ###
67: ### SET CONDITIONING TIMER 2
68: ### SUPERVISES BK2 RECLOSING, ASSERTS IF MOD IS CLOSED AND IN SYNC. AND BK1
69: ### CLOSED OR MOD LATCH SET AND MOD OPEN AND BK2 BUS HOT AND BK1 CLOSED
70: ### FOR FOUR SECONDS
71: PCT02PU := 240.00 # FOUR SECOND PICKUP TIME
72: PCT02DO := 0.0 # NO DELAY ON DROPOUT
73: PCT02IN := NOT IN103 AND 25A1BK2 AND NOT IN101 OR PLT01 AND IN103 AND \
59VS2 AND NOT IN101
Figure 6.53
Protection Free-Form SEL
OGIC
Control Equations (Continued)
Table 6.49
Control Inputs
Input
Monitor Condition
IN101
115 kV BK1T 52 b contact
IN102
115 kV BK2T 52 b contact
IN103
230 kV MOD b contact
IN104
Circuit breaker and autotransformer failure lockouts (86)
Table 6.50
Control Outputs (SEL
OGIC
Control Equations) (Sheet 1 of 2)
Setting
Function
Entry
Main Board
OUT101
Trip BK1T
TRIP
OUT102
Trip BK2T
TRIP
OUT103
Trip MOD
PST01ET > 120.00 AND
NOT PCN01Q
OUT104
Close BK1T
BK1CL
OUT105
Close BK2T
BK2CL
OUT106
Close MOD
PST04ET > 300.00 AND
NOT PCN02Q
OUT107
General alarm
NOT HALARM OR NOT
SALARM OR NOT ILOP
M
IRRORED
B
ITS
Transmit Equations (SEL
OGIC
Control Equations)
TMB1A
Blocking signal
Z3P OR Z3G OR DSTRT
TMB2A
Zone 1 direct underreaching transfer trip
Z1P OR Z1G
TMB3A
Direct transfer trip: 86BF or 86T and MOD closed
NOT IN103 AND IN104
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...