12.4
SEL-400 Series Relays
Instruction Manual
Date Code 20171006
Settings
Multiple Setting Groups
relay defaults to the present active group. If Group 6 is the active group, and you
type
SET <Enter>
, for example, you will see the settings prompts for the
Group 6 settings.
Multiple Setting Groups
SEL-400 series relays have six independent setting groups. Each setting group
has complete relay settings and protection SEL
OGIC
settings. The active setting
group can be:
➤
Shown or selected with the SEL ASCII serial port
GROUP
command—see
➤
Shown or selected from the front-panel LCD with the
MAIN
menu
Set/Show
menu item and the
Active Group
submenu item as
described in
➤
Selected with SEL
OGIC
control equation settings SS1 through SS6.
Settings SS1 through SS6 have priority over all other selection
methods. Use remote bits in these equations to select setting groups
with Fast Operate commands as described in
Operate, Fast SER Messages, and Fast Message Data Access on
page 15.28
.
➤
Shown with DNP3 Objects 20 and 22 and selected with Objects 40
and 41.
Setting Groups: Application Ideas
Setting groups can be used for such applications as:
➤
Environmental conditions such as winter storms, periods of high
summer heat, etc.
➤
Hot-line tag that disables closing and sensitizes protection
➤
Commissioning and operation
Active Setting Group Indication
Only one setting group can be active at a time. Relay Word bits SG1 through SG6
indicate the active setting group, as shown in
.
Table 12.2
Definitions for Active Setting Group Indication Relay Word Bits
SG1 Through SG6
Relay Word Bit
Definition
CHSG
Indication that a group switch timer is operating or a group switch change
is underway
SG1
Indication that setting Group 1 is the active setting group
SG2
Indication that setting Group 2 is the active setting group
SG3
Indication that setting Group 3 is the active setting group
SG4
Indication that setting Group 4 is the active setting group
SG5
Indication that setting Group 5 is the active setting group
SG6
Indication that setting Group 6 is the active setting group
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...