B.5
Date Code 20171006
Instruction Manual
SEL-400 Series Relays
Firmware Upgrade Instructions
Upgrade Procedure
Step 4. Select the
Save calibration settings
check box in the Step 1 of 4
window of the Firmware Loader. These factory settings are required
for proper operation of the relay and must be reentered in the
unlikely event they are erased during the firmware upgrade process.
The Firmware Loader saves the settings in a text file on the PC.
Step 5. Select the
Save device settings
check box if you do not have a copy
of the relay settings. It is possible for relay settings to be lost during
the upgrade process.
Step 6. Select the
Save events
check box if there are any event reports that
have not been previously saved. The event history is cleared during
the upgrade process.
Step 7. Click
Next
.
The Firmware Loader reads the calibration settings and saves them in
a text file on the PC. Make note of the file name and the location.
If
Save device settings
was selected, the Firmware Loader reads all
of the settings from the relay. The software may ask if you want to
merge the settings read from the relay with existing design templates
on the PC. Click
No, do not merge settings with Design Template
.
The Firmware Loader will suggest a name for the settings, but the
suggested name can be modified as desired.
If
Save events
was selected, the
Event History
window will open to
allow the events to be saved. See
for more
information.
Step 8. If you use the Breaker Wear Monitor, click the
Terminal
button in
the lower left portion of the Firmware Loader to open the terminal
window. From the Access Level 1 prompt, issue the
BRE
command
and record the internal and external trip counters, internal and exter-
nal trip currents for each phase, and breaker wear percentages for
each phase.
Step 9. Enable Terminal Logging capture (see
) and
issue the following commands to save stored data. It is possible for
these data to be lost during the firmware upgrade process.
a.
MET E
—accumulated energy metering
b.
MET D
—demand and peak demand
Figure B.1
Prepare the Device (Step 1 of 4)
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...