6.16
SEL-421 Relay
Instruction Manual
Date Code 20171021
Protection Applications Examples
230 kV Overhead Distribution Line Example
EFLOC
Fault Location (Y, N)
Y
LL
Line Length (0.10–999)
50
Relay Configuration (Group)
E21P
Mho Phase Distance Zones (N, 1–5)
2
E21MG
Mho Ground Distance Zones (N, 1–5)
2
E21XG
Quadrilateral Ground Distance Zones (N, 1–5)
N
ECVT
Cvt Transient Detection (Y, N)
N
ESERCMP
Series-compensated Line Logic (Y, N)
N
ECDTD
Distance Element Common Time Delay (Y, N)
Y
ESOTF
Switch-onto-fault (Y, N)
Y
EOOS
Out-of-Step (Y, Y1, N)
N
ELOAD
Load Encroachment (Y, N)
N
E50P
Phase Inst./def.-time O/c Elements (N, 1–4)
1
E50G
Residual Ground Inst./def.-time O/c Elements (N, 1–4)
N
E50Q
Negative-sequence Inst./def.-time O/c Elements (N, 1–4)
N
E51S
Selectable Inverse-time O/c Elements (N, 1–3)
1
E32
Directional Control (Y, AUTO, AUTO2)
AUTO2
ECOMM
Communications-Assisted Tripping (N, DCB, POTT,
POTT2, POTT3, DCUB1, DCUB2)
N
EBFL1
Breaker 1 Failure Logic (N, 1, 2, Y1, Y2)
N
E25BK1
Synchronism Check for Breaker 1 (Y, N, Y1, Y2)
N
E79
Reclosing (Y, Y1, N)
N
EMANCL
Manual Closing (Y, N)
N
ELOP
Loss-of-Potential (Y, Y1, N)
Y1
EDEM
Demand Metering (N, THM, ROL)
N
EADVS
Advanced Settings (Y, N)
N
Mho Phase-Distance Element Reach (Group)
Z1MP
Zone 1 Reach (OFF, 0.05–64
secondary)
1.56
Z2MP
Zone 2 Reach (OFF, 0.05–64
secondary)
2.34
Mho Phase-Distance Element Time Delay (Group)
Z1PD
Zone 1 Time Delay (OFF, 0.000–16000 cycles)
OFF
Z2PD
Zone 2 Time Delay (OFF, 0.000–16000 cycles)
OFF
Mho Ground-Distance Element Reach (Group)
Z1MG
Zone 1 (OFF, 0.05–64
secondary)
1.56
Z2MG
Zone 2 (OFF, 0.05–64
secondary)
2.34
Zero-Sequence Current Compensation Settings (Group)
k0M1
Zone 1 ZSC Factor Magnitude (AUTO, 0.000–10)
AUTO
k0A1
Zone 1 ZSC Factor Angle (–180.0 to +180.0 degrees)
–3.65
Ground Phase-Distance Element Time Delay (Group)
Z1GD
Zone 1 Time Delay (OFF, 0.000–16000 cycles)
OFF
Z2GD
Zone 2 Time Delay (OFF, 0.000–16000 cycles)
OFF
Table 6.6
Settings for 230 kV Overhead TX Example (Sheet 2 of 4)
Setting
Prompt
Entry
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...