14.2
SEL-400 Series Relays
Instruction Manual
Date Code 20171006
ASCII Command Reference
Command Description
89CLOSE
n
Use the
89CLOSE
n
command to close disconnect switches. (The number of
disconnects supported,
n
, depends on the relay.) The main board circuit breaker
jumper (on jumper
BREAKER
) must be in place.
NOTE:
The SEL-487B does not
support disconnect control
operations.
If the disconnect switch is open and Relay Word bit LOCAL is deasserted, the
89CLOSE
n
command asserts Relay Word bit 89CLS
n
for the 89CSIT
n
time.
Disconnect Switch Close and Open Control Logic on page 5.1
. If the Relay
Word bit 89OIP
n
asserts, indicating that the disconnect has started to close, the
relay displays
Operation in Progress...
With Relay Word bit 89OIP
n
asserted
and Relay Word bit 89ALP
n
deasserted, a dot (.) is appended to the above mes-
sage every half second to show progress. While the operation is in progress, com-
munications are unavailable on the port where the
89CLOSE
command was
executed. Assertion of Relay Word bit 89OIP
n
starts the 89ALP
n
alarm timer.
The relay waits for the 89ALP
n
timer to expire and then checks the status of the
89AM
n
and 89BM
n
disconnect inputs. If the 89ALP
n
timer does not expire
within 30 seconds, the relay exits the
89CLOSE
command and reads the status
of the disconnect inputs. The state of Relay Word bits 89AM
n
and 89BM
n
deter-
mine which disconnect status message the relay displays (
Disconnect OPEN
,
Disconnect CLOSED
, or
Status Undetermined - check wiring
). Use the
89CLS
n
Relay Word bit as part of a SEL
OGIC
Output control equation to close
the appropriate disconnect switch.
If the relay is disabled and you attempt an
89CLOSE
n
command, the relay
responds with
Command aborted because the relay is disabled
. If the cir-
cuit breaker control enable jumper
J18C
(BREAKER) is not in place, the relay
aborts the command and responds,
Aborted: the breaker jumper is not
installed
.
When the
89CLOSE
n
command is issued and the circuit breaker control enable
jumper is in place, the relay responds,
CLOSE DISNAM
n
(Y/N)?.
If you answer
Y <Enter>
, the relay responds with
Are you sure (Y/N)?.
If you answer
Y
<Enter>
, the command is executed. If the response to either prompt is not y or Y,
the relay responds with
Command Aborted.
89OPEN
n
Use the
89OPEN
n
command to open disconnect switches. (The number of dis-
connects supported,
n
, depends on the relay.) The main board circuit breaker
jumper (on jumper BREAKER) must be in place.
NOTE:
The SEL-487B does not
support disconnect control
operations.
If the disconnect switch is closed and Relay Word bit LOCAL is deasserted, the
89OPEN n
command asserts Relay Word bit 89OPEN
n
for the 89OSIT
n
time.
Disconnect Switch Close and Open Control Logic on page 5.1
. If the Relay
Word bit 89OIP
n
asserts, indicating that the disconnect has started to open, the
relay displays
Operation in Progress...
With Relay Word bit 89OIP
n
asserted
and Relay Word bit 89ALP
n
deasserted, a dot (.) is appended to the above mes-
sage every half second to show progress. While the operation is in progress, com-
munications are unavailable on the port where the
89OPEN
command was
executed. Assertion of Relay Word bit 89OIP
n
starts the 89ALP
n
alarm timer.
The relay waits for the 89ALP
n
timer to expire and then checks the status of the
89AM
n
and 89BM
n
disconnect inputs. If the 89ALP
n
timer does not expire
Table 14.2
89CLOSE
n
Command
Command
Description
Access Level
8
9CLOSE
n
Set Relay Word bit 89CLS
n
B, P, A, O, 2
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...