![Schweitzer Engineering Laboratories SEL-421-4 Instruction Manual Download Page 384](http://html.mh-extra.com/html/schweitzer-engineering-laboratories/sel-421-4/sel-421-4_instruction-manual_1216726384.webp)
6.48
SEL-421 Relay
Instruction Manual
Date Code 20171021
Protection Applications Examples
500 kV Parallel Transmission Lines With Mutual Coupling Example
Current and Voltage Source Selection (Global)
ESS
Current And Voltage Source Selection (Y, N, 1, 2,
3, 4)
3
LINEI
Line Current Source (IW, COMB)
COMB
BK1I
Breaker 1 Current Source (IW, IX, NA)
IW
BK2I
Breaker 2 Current Source (IX, COMB, NA)
IX
Breaker Configuration (Breaker Monitoring)
EB1MON
Breaker 1 Monitoring (Y, N)
N
EB2MON
Breaker 2 Monitoring (Y, N)
N
BK1TYP
Breaker 1 Trip Type (Single Pole = 1,
Three Pole = 3)
1
BK2TYP
Breaker 2 Trip Type (Single Pole = 1,
Three Pole = 3)
1
Breaker 1 Inputs (Breaker Monitoring)
52AA1
A-Phase N/O Contact Input—BK1
(SEL
OGIC
Equation)
IN101
52AB1
B-Phase N/O Contact Input—BK1
(SEL
OGIC
Equation)
IN102
52AC1
C-Phase N/O Contact Input—BK1
(SEL
OGIC
Equation)
IN103
Breaker 2 Inputs (Breaker Monitoring)
52AA2
A-Phase N/O Contact Input—BK2
(SEL
OGIC
Equation)
IN104
52AB2
B-Phase N/O Contact Input—BK2
(SEL
OGIC
Equation)
IN105
52AC2
C-Phase N/O Contact Input—BK2
(SEL
OGIC
Equation)
IN106
Line Configuration (Group)
CTRW
Current Transformer Ratio—Input W (1–50000)
400
CTRX
Current Transformer Ratio—Input X (1–50000)
400
PTRY
Potential Transformer Ratio—Input Y (1–10000)
4500.0
VNOMY
PT Nominal Voltage (L-L)—Input Y
(60–300 V secondary)
111
PTRZ
Potential Transformer Ratio—Input Z (1–10000)
4500.0
VNOMZ
PT Nominal Voltage (L-L)—Input Z
(60–300 V secondary)
111
Z1MAG
Positive-Sequence Line Impedance Magnitude
(0.05–255
secondary)
3.98
Z1ANG
Positive-Sequence Line Impedance Angle
(5.00–90 degrees)
87.6
Z0MAG
Zero-Sequence Line Impedance Magnitude
(0.05–255
secondary)
14.48
Z0ANG
Zero-Sequence Line Impedance Angle
(5.00–90 degrees)
82.1
EFLOC
Fault Location (Y, N)
Y
LL
Line Length (0.10–999)
75
Table 6.13
Settings for 500 kV Parallel TX Example (Sheet 2 of 7)
Setting
Prompt
Entry
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...