18.9
Date Code 20171006
Instruction Manual
SEL-400 Series Relays
Synchrophasors
Settings for Synchrophasors
PHDV
q
Selects the type of voltages to be included in the synchrophasor data stream
q
.
This setting affects the synchrophasor data packet size.
➤
PHDV
q
:= V1, sends only positive-sequence voltage synchrophasors
of selected terminals.
➤
PHDV
q
:= PH, sends only phase voltage synchrophasors of selected
terminals.
➤
PHDV
q
:= ALL, sends phase and positive-sequence voltage
synchrophasors of selected terminals.
PHDI
q
Selects the type of currents to be included in the synchrophasor data stream q.
This setting affects the synchrophasor data packet size.
➤
PHDI
q
:= I1, sends only positive-sequence current synchrophasors of
selected terminals.
➤
PHDI
q
:= PH, sends only phase current synchrophasors of selected
terminals.
➤
PHDI
q
:= ALL, sends phase and positive-sequence current
synchrophasors of selected terminals.
PHNR
q
Selects the numeric representation, integer (I) or floating-point (F), of voltage
and current phasor data in the synchrophasor data stream
q
. This setting affects
the synchrophasor data packet size.
➤
PHNR
q
:= I sends each voltage and/or current synchrophasor as 2
two-byte integer values. The PMU uses ((7 • I
NOM
• CT Ratio) /
32768) • 100000)) for the current phasor scaling factor and uses
((150 • PTR) / 32768) • 100000)) for the voltage phasor scaling
factor. I
NOM
is 1 A or 5 A.
➤
PHNR
q
:= F sends each voltage and/or current synchrophasor as 2
four-byte floating-point values.
PHFMT
q
Selects the phasor representation of voltage and current phasor data in the syn-
chrophasor data stream q.
➤
PHFMT
q
:= R (rectangular) sends each voltage and/or current
synchrophasor as a pair of signed real and imaginary values.
➤
PHFMT
q
:= P (polar) sends each voltage and/or current
synchrophasor as a magnitude and angle pair. The angle is in radians
when PHNR
q
:= F, and in radians • 10
4
when PHNR
q
:= I. The range
is –
< angle
.
In both the rectangular and polar representations, the values are scaled in root
mean square (rms) units. For example, a synchrophasor with a magnitude of 1.0
at an angle of –30 degrees will have a real component of 0.866, and an imaginary
component of –0.500.
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...