13.16
SEL-400 Series Relays
Instruction Manual
Date Code 20171006
SEL
OGIC
Control Equation Programming
SEL
OGIC
Control Equation Elements
NOTE:
Times for protection timers
must not exceed 2,000,000 cycles for
proper operation.
A conditioning timer output turns on and becomes logical 1, after the input turns
on and the Pickup Time expires. An example timing diagram for a conditioning
timer, PCT01, with a Pickup Time setting greater than zero and a Dropout Time
setting of zero is shown in
. In the example timing diagram, the Input,
PCT01IN, turns on and the timer Output, PCT01Q, turns on after the Pickup
Time, PCT01PU, expires. Because the Dropout Time setting is zero, the Output
turns off when the Input turns off.
If the Pickup Time is not satisfied, the timer Output never turns on, as illustrated
in
. If the input reasserts again, one or more processing intervals later,
the conditioning timer pickup timer begins timing again from zero.
Table 13.9
Conditioning Timer Quantities
Type
Typical Quantity
Name Range
Protection freeform conditioning timers
32
PCT01–PCT32
Table 13.10
Conditioning Timer Parameters
Type
Item
Description
Setting
Name
Examples
Input
Input
Value that the relay times
Boolean SEL
OGIC
control
equation setting
PCT01IN
Input
Pickup
Time
Time that the input must be
on before the output turns on
Time value in cycles
PCT01PU
Input
Dropout
Time
Time that the output stays on
after the input turns off
Time value in cycles
PCT01DO
Output
Output
Timer output
Value for Boolean
SEL
OGIC
control equations
PCT01Q
Figure 13.3
Conditioning Timer With Pickup and No Dropout Timing Diagram
PCT01IN
PCT01Q
Input Changes
from 0 to 1
Input Changes
from 1 to 0
Pickup
Time
PCT01PU
Pickup Time
Expires
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...