5.137
Date Code 20171021
Instruction Manual
SEL-421 Relay
Protection Functions
Trip Logic
Trip Logic
Use the SEL-421 trip logic to configure the relay for tripping one or two circuit
breakers. You can apply the SEL-421 in single-pole tripping applications, three-
pole tripping applications, or both. Set the SEL-421 to trip unconditionally (as
with step distance) or with the aid of a communications channel (as with the
POTT, DCUB, DCB, and DTT schemes).
Three-Pole Tripping
The relay uses three-pole tripping logic if Relay Word bit E3PT (three-pole trip
enable SEL
OGIC
control equation) equals logical 1. You can set E3PT to 1 or
assign a control input so that an external condition changes the state of this Relay
Word bit.
There are separate three-pole tripping SEL
OGIC
control equations for two circuit
breakers, E3PT1 and E3PT2, respectively. When you set E3PT1 or E3PT2 to 1,
the corresponding circuit breaker trips three pole only. For details on setting
E3PT, E3PT1, and E3PT2, see
Trip Logic and Reclose Sources for Single-Pole
Breaker Applications on page 6.9
Trip Logic and Reclose Sources for Single-
Pole Breaker Applications on page 6.25 in the SEL-400 Series Relays Instruction
Manual
.
Single-Pole Tripping
The relay uses single-pole tripping logic if Relay Word bit E3PT, three-pole trip
enable SEL
OGIC
control equation, equals logical 0. You can either set E3PT to 0
or assign a control input so that an external condition changes the state of this
Relay Word bit.
The SEL-421 automatically single-pole trips for the following conditions when
the single-pole tripping logic is active:
➤
Zone 1 ground-distance protection asserts for a single phase-to-
ground fault
➤
Zone 2 ground-distance protection asserts for a single phase-to-
ground fault and is permitted to trip via the communications-assisted
tripping logic
➤
Any one of three SEL
OGIC
control equations, DTA, DTB, or DTC, is
assigned to an input and asserts (per-phase direct transfer trip)
You can also set the SEL-421 to single-pole trip through the following three
options:
Table 5.76
Additional Settings for Single Pole Tripping (SPT)
Setting
Prompt
Selection
Z2GTSP
Zone 2 Ground Distance Time Delay Single-Pole Trip
Y
67QGSP
Zone 2 Directional Negative-Sequence/Residual Ground
Overcurrent Single Pole Trip
Y
EWFC
a
a
In POTT and DCUB settings.
Weak-Infeed Trip
SP
b
b
SP = single pole.
Summary of Contents for SEL-421-4
Page 6: ...This page intentionally left blank ...
Page 14: ...This page intentionally left blank ...
Page 30: ...This page intentionally left blank ...
Page 104: ...This page intentionally left blank ...
Page 128: ...This page intentionally left blank ...
Page 536: ...This page intentionally left blank ...
Page 584: ...This page intentionally left blank ...
Page 616: ...This page intentionally left blank ...
Page 696: ...This page intentionally left blank ...
Page 750: ...This page intentionally left blank ...
Page 755: ...Instruction Manual PM400 01 NB SEL 400 Series Relays Instruction Manual 20171006 ...
Page 776: ...This page intentionally left blank ...
Page 932: ...This page intentionally left blank ...
Page 976: ...This page intentionally left blank ...
Page 1024: ...This page intentionally left blank ...
Page 1038: ...This page intentionally left blank ...
Page 1064: ...This page intentionally left blank ...
Page 1128: ...This page intentionally left blank ...
Page 1206: ...This page intentionally left blank ...
Page 1316: ...This page intentionally left blank ...
Page 1350: ...This page intentionally left blank ...
Page 1464: ...This page intentionally left blank ...
Page 1468: ...This page intentionally left blank ...
Page 1492: ...This page intentionally left blank ...
Page 1518: ...This page intentionally left blank ...